Samsung Electronics
288
Key Options
8-4 How to check the view mode using a tact switch (cont.)
Optional item
Input unit SEG1 SEG2 SEG3 SEG4
Function of the option
Remarks
Emergency opera-
tion for compressor
malfunction
Individual
0
0
0
0
Disabled (Factory default)
E560 will occur when all the compres
-
sors are set as malfunction state.
0
1
Set compressor 1 as malfunction state
0
2
Set compressor 2 as malfunction state
Capcity correction
for cooling
Main
0
1
0
0
7-9 (Factory default)
Targeted evaporation temperature
[°C]. (When low temperature value is
set, discharged air temperature of the
indoor unit will decrease)
0
1
5-7
0
2
9-11
0
3
10-12
0
4
11-13
0
5
12-14
0
6
13-15
Capcity correction
for heating
Main
0
2
0
0
3.0 (Factory default)
Targeted high pressure [MPa].
(When low pressure value is set, dis
-
charged air temperature of the indoor
unit will decrease)
0
1
2.5
0
2
2.6
0
3
2.7
0
4
2.8
0
5
2.9
0
6
3.1
0
7
3.2
0
8
3.3
Current
restriction rate
Individual
0
3
0
0
100% (Factory default)
When restriction option is set,
cooling and heating
performance may decrease
0
1
95 %
0
2
90 %
0
3
85 %
0
4
80 %
0
5
75 %
0
6
70 %
0
7
65 %
0
8
60 %
0
9
55 %
1
0
50 %
1
1
No restriction
Oil collection interval
Main
0
4
0
0
Factory default
0
1
Shorten the interval by 1/2
Temperature to
trigger defrost
operation
Main
0
5
0
0
Factory default
0
1
Apply setting when the product is
being installed in humid area such as
near river or lake
Fan speed correction
for outdoor unit
Individual
0
6
0
0
Factory default
Silent mode
Main
0
7
0
0
Disabled (Factory default)
Enable the silent mode for
night-time in cooling mode (Itoperates
automatically depending on the tem-
perrature.)
However, if the external contact
ineterface module(MIM-B14) is used,
entering the silent mode is available
with contact signal in cooling and heat
-
ing mode.
0
1
LEVEL 1 / Auto
0
2
LEVEL 2 / Auto
0
3
LEVEL 3 / Auto
0
4
LEVEL 4 / External contact
0
5
LEVEL 5 / External contact
0
6
LEVEL 6 / External contact
0
7
LEVEL 1
0
8
LEVEL 2
0
9
LEVEL 3
■
AM080/100/120/140/160/180/200/220/240/260AXVGGH, AM080/100/120/140/160/180/200/220/240/260AXVGGR,
AM080/100/120/140/160/180/200/220/240/260AXVAGH, AM100/120/140/160/180AXVDGH