Piping Diagram
Samsung Electronics
275
Fan speed correction for outdoor unit
▪
Purpose
Improve performance in cooling mode when the outdoor temperature is high or in heating mode when the outdoor tem
-
perature is low.
▪
Concept
The maximum fan RPM rises to the limit if this option is configured. (The RPM does not change on some models.)
▪
Control specifications in detail
-
High pressure is controlled taking into account the maximum fan RPM.
- See "Fan control" for details on outdoor fan operation specifications.
Input unit
Seg1
Seg2
Seg3
Seg4
Temperature to trigger defrost operation
Individual
0
6
0
0
Standard (default)
0
1
Increase fan speed
▪
Notes
- Noise level may increase as the maximum RPM rises.
- Do not configure this option if using units in a location that is outside the recommended operation temperature (48
℃
)
or permitted external static pressure
7-3 Functions (cont.)
7-3-3-1 Field Setting (cont.)
7-3-3 Others (cont.)