INS
TALLA
TION
Water pipe installation
26
English
Securing water storage
Minimum water storage
Chilled/
heating
water pump
Buffer tank
Fan coil
f
If the length of water pipe is too short, water storage
within the system becomes lower and ON/OFF
operation of the compressor occurs more often. For
stable operation, maintain certain water storage by
applying header or Buffer tank.
CAUTION
ŷ
When installing tank, inlet pipe of the tank must be
installed under the water level.
f
If total water storage becomes under the minimum
storage, install another tank to retain more water
storage.
- In case of variable flow system, retain certain
amount of water by bypass pipe system.
Unit : L (gal)
Model name
Minimum water storage
AG010KSV Series
272.5 (72)
AG015KSV Series
381.6 (100.8)
NOTE
ŷ
Total water storage in the system = water storage
within the water pipe + water storage in DVM
C water storage in AHU (or fan coil)
ŷ
Minimum capacity of buffer tank = Minimum
water storage - Total water storage in the system
excluding buffer tank
ŷ
Select the capacity of buffer tank according to
system installation condition of the field.
ŷ
Water amount within the DVM CHILLER: 3.17 gal
Water pipe installation
Connecting water pipe
Chilled/heating water inlet
Chilled/heating water outlet
f
Companion coupling is not supplied. Use field
supplied one in ASME standardized product.