INS
TALLA
TION
14
English
Required space for installation
f
Space requirement is based on the following
conditions; Cooling mode, outdoor temperature of
35°C (95°F). Larger space is required if the outdoor
temperature is higher than 35°C (95°F) or if the place
is heated easily by extreme solar radiation.
f
When you secure installation space, consider path for
people and the direction of the wind.
f
Secure installation space as shown in the figure,
considering ventilation and the service space.
f
If the installation space is narrow, installer or other
worker may get injured during work and may also
cause a problem with the product.
f
If you install multiple number of DVM CHILLERs in
one space, make sure to secure enough ventilation
space if there's any walls around the product that
may disturb the air flow. If enough ventilation space
is not secured, the product may malfunction.
f
DVM CHILLERs can be installed with 4 inches
between each unit, but performance may decrease
depending on the installation environment. More
than 4 inches is recommended.
1
Single installation
Unit: mm (inch)
Front side
100 (4) or more
100 (4) or
more
500 (20) or
mor
e (S1)
100 (4) or
mor
e (S2)
<Case 1>
Front side
100 (4) or
more
300 (12) or
more
Height of
the wall is
unlimited
<Case 2>