How to set hydro controller option
Option No.
Option value
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
Operation On/Off input
method
0
1
-
-
-
0
Temperature setting input
method
0
2
-
-
-
0
1
Turn on the product.
2
Press and hold the K2 to enter the option setting.
f
In option setting, other key input (forced fan, temperature setting, etc.) is not received.
3
Press K1 shortly to display the number for selected option.
4
Press K2 shortly to display the number for set value of the selected option.
5
Finish the option setting.
f
Press K2 long to finish the setting with all option values determined and saved.
f
Press K1 long to finish the setting with all option values cancelled and keep the values as before entering the
setting.
ŷ
In option setting, press K4 long to initialize all option values.
No.
Option item
Option
value
Factory
default
Option
Definition
Setting unit
Module
control
setting
option
Note1)
1
Operation On/Off input method
0·1
0
0
Module control/DMS
Main unit
of group
Note2)
1
External contact
2
Temperature setting input method
0·1
0
0
Module control/DMS
Main unit
of group
Note2)
1
External contact
3
Operation mode (Cool/Heat,
normal/hot water) input method
0·1
0
0
Module control/DMS
Main unit
of group
Note2)
1
External contact
4
Demand control input method
0·1
0
0
Module control/DMS
Main unit
of group
Note2)
1
External contact
5
Demand level
0 ~ 11
3
0
Default (100 %)
Main unit
of module
O
1
95 %
2
90 %
3
85 %
4
80 %
5
75 %
6
70 %
7
65 %
8
60 %
9
55 %
10
50 %
11
Not applied (No limit)