ELE
CTRIC
AL W
ORK
47
English
No.
Option item
Option
value
Factory
default
Option
Definition
Setting unit
Module
control
setting
option
Note1)
16
AirCool1 (For water law)
0 ~ 20
10
Standard 1 outdoor temperature
for cooling
Main unit
of group
Note2)
O
17
AirCool2 (For water law)
30 ~ 40
35
Standard 2 outdoor temperature
for cooling
18
RoomCool1 (For water law)
15 ~ 24
20
Standard 1 room temperature for
cooling
19
RoomCool2 (For water law)
25 ~ 35
30
Standard 2 room temperature for
cooling
20
Tcool1 (For water law)
-10 ~
25
15
Standard 1 set temperature for
cooling
21
Tcool2 (For water law)
-10 ~
25
7
Standard 2 set temperature for
cooling
22
AirHeat1 (For water law)
-20 ~ 5
-10
Standard 1 outdoor temperature
for heating
23
AirHeat2 (For water law)
10 ~ 20
15
Standard 2 outdoor temperature
for heating
24
RoomHeat1 (For water law)
15 ~ 24
20
Standard 1 room temperature for
heating
25
RoomHeat2 (For water law)
25 ~ 35
30
Standard 2 room temperature for
heating
26
Theat1 (For water law)
35 ~ 55
45
Standard 1 set temperature for
heating
27
Theat2 (For water law)
35 ~ 55
35
Standard 2 set temperature for
heating
28
Operation ON/OFF by external
contact
0/1
0
0
Recognize usual signal
Main unit
of group
Note2)
1
Recognize instant signal
29
~
33
Function expansion available
34
Using low temperature function
0/1
0
0
Disuse
Each unit
1
Use
35
~
37
Function expansion available
Note1)
For options that can be selected by module control and main option, the option value selected for last time will
be saved.
Note2)
Main unit of module when group is not available