INS
TALLA
TION
13
English
f
Protection wall should be constructed with a solid
material that can block the sea breeze and the height
and width of the wall should be 1.5 times larger
than the size of the DVM CHILLER. (You must secure
more than 700 mm (27.6 inch) of space between
the protection wall and the DVM CHILLER for air
circulation.)
Sea
Sea breeze
DVM
CHILLER
Protection wall
DVM
CHILLER
CAUTION
ŷ
In regions with heavy snowfall, make sure to install
the DVM CHILLER where there are no concerns of
direct snowfall on the DVM CHILLER. Also, build
higher base support so that accumulated snow does
not block the air inlet or the heat exchanger.
ŷ
R-410A refrigerant is a safe, nontoxic and
nonflammable refrigerant. However, if the place
holds any concerns for exceeding dangerous level
of refrigerant concentration in case of refrigerant
leakage, extra ventilation system is required.
ŷ
When you install the product on a high location
such as roof, install fence or guardrail around it.
When there is no fence or guardrail, the service
person could fall.
ŷ
Do not install the product in places where corrosive
gases such as sulfur oxides, ammonia, and sulfurous
gases are produced. (e.g. Toilet outlet, ventilation
opening, sewage works, dyeing complex, cattle
shed, sulfuric hot spring, nuclear power plant, ship
etc.) When installing the product in those places,
contact an installation specialty store as the copper
pipe and brazing part will need additional corrosion
proof or anti-rust additive to prevent corrosion.
ŷ
Make sure to keep any inflammable materials (such
as wooden materials, oil etc.) around the DVM
CHILLER. When there's fire, those inflammable
material will easily catch the fire and may pass it on
to the product.
ŷ
Depending on the condition of power supply,
unstable power or voltage may cause malfunction
of the parts or control system.
(At the ship or places using power supply from
electric generator, etc.)
Summary of Contents for AG010KSV Series
Page 85: ...MAINTENANCE 85 English MEMO ...