Is the strainer in water pipe contaminated after the
trial operation?
- Clean the strainer if contaminated.
f
Is minimum amount of circulating water (over 50 %
of rated flow rate) acquired?
Trial operation for each CHILLER
unit
HYDRO-UNIT_MODULE_CHILLER
.ř
.Ś
.ś
.Ŝ
.ŝ
.Ş
.ř
.Ś
.ś
.Ŝ
.ŝ
.Ş
ON
OFF
88-SEG DISPLAY
TACT S/W
DIP S/W
1
Turn on the product.
2
Check if DIP S/W 1 is on.
DIP S/W
No.1
On
Off
Main control
Remote control
NOTE
ŷ
When set as main control, the product does not
receive any control of external contact, module
control, and upper controller, and any orders from
module/group control.
ŷ
In order to use the module control after a trial
operation, turn off (downward) the DIP S/W 1.
3
Water side pressure sensor calibration
f
Sensor calibration operates for more precise water
rate inspection.
f
It operates in main control only.
f
Water flow in the system must not exist when
calibrating sensor.
f
Press and hold K4 and K6 for 3 seconds to start the
calibration when operation of the product and the
pump is off.
Seg1
Seg2
Seg3
Seg4
Seg5
Seg6
K
C
A
L
I
f
The operation will finish automatically within 30
seconds.
f
The product and the pump cannot be operated while
calibrating the pressure difference.
4
Forced fan function removes accumulated snow on
the fan. Skip this step if snow is not accumulated.
f
Press and hold K6 for 3 seconds when operation is
off and the fan will operate.
Seg1
Seg2
Seg3
Seg4
Seg5
Seg6
K
F
A
N
f
During forced fan function, press K6 and the
operation will stop.
- If the operation is on during forced fan function,
the fan will stop.
5
Forced pump function checks if water flow is normal.
f
Press and hold K5 for 3 seconds when operation is
off and the pump will operate.
Seg1
Seg2
Seg3
Seg4
Seg5
Seg6
K
P
U
M
P
f
During forced pump function, press K5 and the
operation will stop.
- If the operation is on during forced pump
function, the pump will stop.
6
Operation mode in main control is selected be
cooling/heating switch.
DIP S/W
No.2
On
Off
Cool mode
Heat mode
f
Operation mode can be changed only when operation
is off.