SECTION 4 |
Parameter Setup
• If the battery voltage drops to “LOW VOLT ALARM” [(i) for 12V: 9.5V – 12.5V / Default
11.0V (ii) for 24V: 19.0V – 25.0V / Default 22.0V] or lower for continuous period =
“GS DETECT TIME” (0-600 sec; Default 10 sec), the Status Relay will be switched ON
(energized). “Common” and “NO” contacts of the Status Relay will close to initiate
automatic starting of the Generator.
• Once the generator has started and starts feeding AC output (within the programmed
limits of voltage and frequency), the EVO
TM
will change over from “Inverting Mode” to
“Charging Mode”. Battery charging will be initiated as per full and complete 3-Stage
Charging Algorithm (“EQUALIZE-4STAGES", Option 0 = No).
• The Status Relay will be switched OFF (de-energized) after expiry of the desired
programmed Generator run time = “GEN ON TIME” (0-240 min; Default = 60 min)
counted from the time the Status Relay is switched ON (energized). “Common” and
“NO” contacts of the Status Relay will open to initiate automatic stopping of the
Generator. When AC output from the Generator switches OFF, EVO
TM
will change over to
“Inverting Mode” (
NOTE:
The State of Charge of the battery after the Status Relay has
been switched OFF (de-energized) and Generator is stopped will be indeterminate).
Diagram showing steps for programming the above RELAY FUNCTION is given below:
Password 8052
See Section 4.3.1
S e l e c t
G r o u p
*
C H A R G E
C U R V E
ð
S e l e c t
P a r a m e t e r
*
O T H E R
F U N C T I O N
ð
S e l e c t
P a r a m e t e r
O T H E R
F U N C T I O N
*
P O W E R
S A V I N G
0 = D i s a b l e
S e l e c t
P a r a m e t e r
O T H E R
F U N C T I O N
*
R E L A Y
F U N C T I O N
2 = G e n e r a t o r
0
Down Key x 4 times
Enter Key
Down Key x 4 times
ð
P a s s w o r d
k e y
i n
0 0 0 0
ð
S e l e c t
P a r a m e t e r
O T H E R
F U N C T I O N
*
R E L A Y
F U N C T I O N
2 = G e n e r a t o r
0
Enter Key
4.8.2.6
COMM ID
(Table 4.8, Screen No. 6)
Communication ID- This sets the ID number for the COMM Port and EVO-RC Remote Control.
Password 8052
See Section 4.3.1
S e l e c t
G r o u p
*
C H A R G E
C U R V E
ð
S e l e c t
P a r a m e t e r
*
O T H E R
F U N C T I O N
ð
S e l e c t
P a r a m e t e r
O T H E R
F U N C T I O N
*
P O W E R
S A V I N G
0 = D i s a b l e
S e l e c t
P a r a m e t e r
O T H E R
F U N C T I O N
*
C O M M . I D
1
Down Key x 4 times
Enter Key
Down Key x 5 times
ð
P a s s w o r d
k e y
i n
0 0 0 0
ð
S e l e c t
P a r a m e t e r
O T H E R
F U N C T I O N
*
C O M M . I D
1
Enter Key
Enter Key
ð
See Table 4.8, Screen No. 5
for programmable options
Enter Key
ð
See Table 4.8, Screen No. 6
for programmable options