PDS51 Series
- 31 -
Parameter
Name
Setting Range
Default
Value
Remarks
Fea-
ture
Communi
-cation
Address
0: off
1: On
FA.20
Fault
self-recovery
times
0
~
5
3
Select 1 to 5 to
enable automatic
fault reset operation.
When there is a fault
during operation, the
fault will be reset
automatically after
fixing for 10S. Water
shortage,
disconnection, high
and low voltage, pipe
burst, external fault,
and time arrival fault
are not affected by
this function code.
☆
0xA14
FD Team
:
Specific Solar Pump Controller Parameters
FD.00
Solar Pump
Running Option
0
:
Invalid
1
:
Valid
1
●
FD00
FD.01
Runing Mode
Option
0: PV Input Mode
1: PV Priority Mode
2: Power Priority Mode
1
0: PV input refers to
only PV DC power
supply
(
No AC
input
)
;
1: PV priority mode,
which means that
when AC and DC
input power are both
connected at the
same time, the PV
power will be used
first, and the AC will
be automatically
connected when the
PV power is
insufficient.
2: Power priority
mode, when AC and
DC input are both
●
0xD00