PDS51 Series
- 28 -
Parameter
Name
Setting Range
Default
Value
Remarks
Fea-
ture
Communi
-cation
Address
7
:
Terminal UP/DOWN
8
:
MPPT
9
:
RS 485 Communication
10
:
Multi-Drive
Communication
F0.08
Keypad Setting
Maximum
Frequency
0.00
~
F0.10
50.00Hz
○
0x008
F0.09
Motor Rotation
Direction
0
:
FWD
1
:
REV
0
○
0x009
F0.10
Maximum
Output
Frequency
50.00
~
320.00Hz
50.00Hz
●
0x00A
F0.12
Upper Limit of
Running
Frequency
F0.14
~
F0.10
50.00Hz
○
0x00C
F0.14
Lower Limit of
Running
Frequency
0.00
~
F0.12
0.00Hz
○
0x00E
F0.15
Running Mode
at F0.14
0: Standby(Sleep)
1: Running at F0.14
2: Stop
0
○
0x00F
F0.16
Carrier
Frequency
0.5
~
15.0kHz
Due to
Controller
Model
8.0 as maximum for
SVC mode
○
0x010
F0.18
Acceleration
Time1
0.0
~
6500.0s
Due to
Controller
Model
○
0x012
F0.19
Deceleration
Time1
0.0
~
6500.0s
Due to
Controller
Model
○
0x013
F0.20
Recover Option
0: No Option
1: Recover all default
settings,except F2 team
2: Clear all error
(
alarm
)
records
3: Recover all default
0
●
0x014