8000m Series
- 82 -
5
Jog reverse (RJOG)
reverse operation. As for the frequency and the
acceleration and deceleration time of jog
operation, refer to the detailed description of
function code of F8.00, F8.01 and F8.02.
6
Coast to stop
The VFD blocks output, the shutdown process of
electric motor is not controlled by the VFD. As for
large inertia loads and no requirements for the
time of shutdown, this is the usual method. The
definition of this method is the same as that
defined in F1.05.
7
Fault reset (RESET)
External fault reset function. This function is the
same as that of RESET on keyboard. Remote fault
reset is implemented by this function.
8 Pause
running
The VFD slows down, but all the operating
parameters are in memory state, such as PLC, the
swing frequency, and PID parameters. As soon as
this signal disappears, the VFD returns to the
status before shutdown.
9
External fault input N. O.
Set the terminal as this function, as this terminal
closed, the VFD will report E015 fault and stop.
10
Frequency setting
increasing(UP)
If the frequency is determined by external
terminals, the terminals with the two functions are
used as increment and decrement commands for
frequency modification.
When the frequency source is digital setting, they
are used to adjust the frequency.
11
Frequency setting
decreasing(DOWN)
12 Clear
UP/DOWN
setting
Clear the frequency values set through
UP/DOWN.
13
Frequency setting source
switch between X and Y
If the present frequency source is X, switch to
frequency source Y.
14
Frequency setting source
switch between X and
(X+Y)
If the present frequency source is X, switch to
frequency source X+Y.
15
Frequency setting source
switch between Y and
If the present frequency source is Y, switch to
frequency source X+Y.