8000m Series
- 83 -
(X+Y)
16
Multi-step speed terminal 1
The setting of 16 speeds can be implemented
through combinations of these four terminals. For
details, please refer to annex 1.
17
Multi-step speed terminal 2
18
Multi-step speed terminal 3
19
Multi-step speed terminal 4
20 Multi-step
speed
pause
Shield the terminal function of multi-step speed
selection, and maintain the setting value to current
status.
21
Acceleration/deceleration
time selection terminal 1
Select 4 settings of acceleration and deceleration
time by the combine of the digit status of these
two terminals.
22
Acceleration/deceleration
time selection terminal 2
23
Restart simple PLC after
pause
Restart the process of simple PLC and clear up the
memory information of the previous PLC
24
Simple PLC pause
Executing process of simple PLC pauses, operate
all the time at the current speed
25 PID
pause
PID is invalid temporarily, the VFD maintains the
present output of frequency, will not adjust by
PID.
26
Swing frequency pause
(maintain at current
frequency)
The VFD maintains temporarily at the present
output of frequency
27
Reset after swing frequency
pause (reset to central
frequency)
The frequency of the VFD resets to central
frequency
28
Counter reset
This will clear up the status of counter
29 Reserved
30
Acceleration/deceleration
prohibited
Keep the VFD not influenced by outer
signals(except the stop command), maintains the
present output frequency.
31 Counter
triggering
32
Clear UP/DOWN setting
temporarily
When the terminal is closed, this can clear up the
set frequency of UP/DOWN; when the terminal is