8000m Series
- 75 -
Under speed control mode, the VFD output the maximum value of torque, set
100.0% which is correspondent to the rated output(or rated torque) current of the
VFD.
0
:
no detection
1: Overload pre-alarm is detected effective in operation (including acceleration,
deceleration and constant speed), go on operation after detection
2: Overload pre-alarm is detected effective in operation (including acceleration,
give alarm (E023) and stop after detection
3: Overload pre-alarm is detected effective in constant speed, go on operation after
detection
4: Overload pre-alarm is detected effective in constant speed, go on operation after
detection, give alarm (E023)and stop after detection
F3.07
Upper limit torque
Factory Setting
150%
Setting Options
0.0
~
200.0% (Drive rated current)
F3.08-F3.09 Reserved
F3.10
Pre-alarm option when overload
Factory Setting
1
Setting Options
0
~
4
F3.11
Detecting level of pre-alarm when
overload
Factory Setting
150.00%
Setting Options
1.0~200.0% (referred to inverter
rated current)
F3.12
Detecting time of pre-alarm when
overload
Factory Setting
1s
Setting Options
0~600s