OPC90 Server
7.27
Remote Manual Set Constant (RMSC)
The RMSC OPC90 block is used to retrieve and control the exception reported
output from Bailey Remote Manual Set Constant blocks (function code 68).
Restrictions: This OPC90 block can be utilized with all Bailey interface types
except serial port module (SPM & CPM02).
Warning: Do not use a series of these blocks to provide bulk transfer of data
between the client and ABB Bailey controller. Instead use the OPC90 AOL block
to source the client data and ABB Bailey AI/I (FC 121) or AI/L (FC 26) blocks in
the controller to receive the data.
TAGNAME TYPE
ACCESS
DESCRIPTION
ADDR_RING VT_I2
Config/Read
Bailey ring address.
ADDR_NODE VT_I2
Config/Read
Bailey node address.
ADDR_MODULE VT_I2
Config/Read
Bailey module address.
ADDR_BLOCK VT_I2
Config/Read
Bailey block address.
MESSAGE
VT_BSTR
Read
Provides the block operational message.
TAG
VT_BSTR
Read
Provides the block name.
TAGLONG VT_BSTR
Read
Provides
the block long OPC path name.
TAGDESC
VT_BSTR
Read
Provides the block descriptor.
QUALITY VT_BOOL
Read Current
quality of Bailey values (0-good, 1-
bad).
EU
VT_I2
Read
Engineering Units Code.
EU_TEXT
VT_BSTR
Read
Engineering Units String.
OUT
VT_R4
Read/Write
Current output value received from Bailey.
OUT_HI_LIM
VT_R4
Read
OUT high limit.
OUT_LO_LIM
VT_R4
Read
OUT low limit.
SP_TRACKING
VT_BOOL
Read
Set point is tracking indicator.