Electrical connection options
Cable type 6, cable diameter 7.4
mm
1-wire with spring return with con-
figurable spring return period con-
tinuous [p.22]
1-wire with spring return with con-
stant spring return period continuous
[p.22]
1-wire with spring return continu-
ous without feedback signal [p.23]
3-point with spring return with con-
figurable spring return period con-
tinuous feedback signal [p.23]
3-point with spring return with con-
figurable spring return period con-
tinuous [p.24]
3-point with spring return constant
spring return period continuous [p.25]
Activation CONTROL
min.
typ.
max.
unit
Angle of rotation and position indicator
95
°
Precision electrical*
~100
Step
Activation Y
0
4
10
20
VDC
mA
Performance data Y and U
• Activation Y
U
(for 10
k
Ω
output impedance)
• Activation Y
I
(for 100
Ω
load / output impedance)
• Feedback U
U
(for 10
k
Ω
…
∞ Ω
input impedance)
• Feedback U
I
(for 0…800
Ω
load / input impedance)
0
4
0
4
10
20
10
20
VDC
mA
VDC
mA
Inverting
Setting up wire bridges between ter-
minals 3 and 4
Environmental conditions
min.
typ.
max.
unit
Humidity (not condensing)
90
% rH
Protection class as per DIN EN 60529
IP66
Operation
• Ambient temperature (T6)
• Ambient temperature (T5)
–40
–40
+40
+50
°C
°C
3 | Device description
74
Translation of the original installation guide · Version 1.0 · 2021-05-27