Electrical characteristics
min.
typ.
max.
unit
Power consumption standby*
5
W
Power consumption heating mode*
16
W
Power consumption in operation
Power consumption as a function of
Switch-on peak
• at 24
VDC (for approx. 2 seconds)*
• at 240
VDC (for approx. 2 seconds)*
2
2
A
A
Maximum duty cycle for motor run time
7.5
s, 15
s, 30
s, 60
s, 120
s
100
%
Electrical connection options
Cable type 5+PE, cable diameter 7.5
mm
1-wire with spring return with con-
figurable spring return period [p.26]
3-point with spring return with con-
figurable spring return period [p.26]
1-wire with spring return continu-
Without spring return continuous
Activation CY-drives
min.
typ.
max.
unit
Power supply / frequency
Minimum voltage
–10
%
24
+10
% VAC/DC
Maximum voltage
–10
%
240
+10
% VAC/DC
Minimum frequency
–20
%
50
+20
%
Hz
Maximum frequency
–20
%
60
+20
%
Hz
Activation Y
4
20
mA
Feedback signal U
0
10
VDC
Performance data Y and U
• Activation Y
U
(for 10
k
Ω
)
• Feedback U
U
(for 2000
k
Ω
…
∞ Ω
)
0
0
10
10
VDC
VDC
Environmental conditions
min.
typ.
max.
unit
Humidity (not condensing)
90
% rH
Protection class as per DIN EN 60529
IP66
3 | Device description
Translation of the original installation guide · Version 1.0 · 2021-05-27
81