3.7.1.6.8 3-point with spring return with configurable spring return period
continuous
Self-adaptation:
24...240 VAC/DC
~
~
–
+
PE
1
2
3
4
PA
a
b
1
2
3
4
5
6
YmA YVDC
T
VDC/mA UmA UVDC
Function and override control in continuous mode:
▪ b closed - forced-CLOSED (OPEN), depending on left/right installation of the drive
Bridge 3 – 4 inverts
the input and
feedback signals
Inverse operation:
5
Spring return in ~ 10 s = default connection
Spring return in ~ 3 s = additional bridge to
terminal 5
Runtime option for spring-return drives:
▪ a closed - forced-OPEN (CLOSED), depending on left/right installation of the drive
Automatic alignment of positioning signal
and feedback signal with regard to the
angle of rotation (or travel) is done by
pressing the button (T) for at least 3 s.
Fig.
35: SB5.0 - cable type 5+PE, cable diameter 7.5
mm / cable type 6, cable diameter
7.4
mm
For explanation of the function of switches "a" and "b" see:
.
3 | Device description
36
Translation of the original installation guide · Version 1.0 · 2021-05-27