Electrical connection options
Cable type 5+PE, cable diameter 7.5
mm
1-wire with spring return with con-
figurable spring return period [p.26]
3-point with spring return with con-
figurable spring return period [p.26]
1-wire with spring return continu-
Without spring return continuous
Activation CY-drives
min.
typ.
max.
unit
Power supply / frequency
Minimum voltage
–10
%
24
+10
% VAC/DC
Maximum voltage
–10
%
240
+10
% VAC/DC
Minimum frequency
–20
%
50
+20
%
Hz
Maximum frequency
–20
%
60
+20
%
Hz
Activation Y
4
20
mA
Feedback signal U
0
10
VDC
Performance data Y and U
• Activation Y
U
(for 10
k
Ω
)
• Feedback U
U
(for 2000
k
Ω
…
∞ Ω
)
0
0
10
10
VDC
VDC
Environmental conditions
min.
typ.
max.
unit
Humidity (not condensing)
90
% rH
Protection class as per DIN EN 60529
IP66
Operation
• Ambient temperature (T6)
• Ambient temperature (T5)
–40
–40
+40
+50
°C
°C
Storage
• Ambient temperature
–40
+70
°C
*: Nominal value: please note that nominal values are also subject to tolerances. For more
detailed information, see:
3 | Device description
118
Translation of the original installation guide · Version 1.0 · 2021-05-27