3.7.1.2.6 1-wire with spring return continuous without feedback signal
Self-adaptation:
24...240 VAC/DC
~
~
–
+
PE
1
2
3
4
PA
1
2
3
4
5
6
YmA YVDC
T
VDC/mA
Bridge 3 – 4 inverts
the input signals
Inverse operation:
5
Spring return in ~ 10 s = default connection
Spring return in ~ 3 s = additional bridge to
terminal 5
Runtime option for spring-return drives:
Automatic alignment of positioning signal
and feedback signal with regard to the
angle of rotation (or travel) is done by
pressing the button (T) for at least 3 s.
Fig.
12: SB5.2 - cable type 5+PE, cable diameter 7.5
mm / cable type 6, cable diameter
7.4
mm
3.7.1.2.7 3-point with spring return with configurable spring return period
continuous feedback signal
Self-adaptation:
24...240 VAC/DC
~
~
–
+
PE
1
2
3
4
PA
a
b
1
2
3
4
5
6
T
VDC/mA UmA UVDC
3-pt activation:
Bridge 3 – 4 inverts the
feedback signals
Inverse operation:
5
Spring return in ~ 10 s = default connection
Spring return in ~ 3 s = additional bridge
to terminal 5
Runtime option for spring-return drives:
Caution!
When converting
from continuous to
3-point mode note
function
▪ b closed, a open - CLOSED (OPEN), depending on left/right installation of the drive
▪ a closed, b open - OPEN (CLOSED), depending on left/right installation of the drive
Automatic alignment of positioning signal
and feedback signal with regard to the
angle of rotation (or travel) is done by
pressing the button (T) for at least 3 s.
Fig.
13: SB5.3 - cable type 5+PE, cable diameter 7.5
mm / cable type 6, cable diameter
7.4
mm
3 | Device description
Translation of the original installation guide · Version 1.0 · 2021-05-27
23