Contact S1 - Function
r1
Contact S1 - Value
r1
Indication contacts S1 [r1], S2 [r2], S3
[r3] and S4 [r4] may each be set to trip
for any one of the following functions:
Code
Function
[CL]
closed end position
[OP]
open end position
[Po]
intermediate position
[tC]
torque trip close
[tO]
torque trip open
[tt]
torque trip any position
[tl]
torque trip mid travel
[dC]
actuator closing
[dO]
actuator opening
[d?]
actuator rotating
[St]
motor stalled
[bA]
battery low
[HA]
hand operation
[bL]
blinker
[LS]
local stop
[Ol]
open interlock
[Cl]
close interlock
[lL]
interlock active
[ES]
ESD signal
[LP]
lost phase
[Lo]
local selected
[
r
E]
remote selected
[AA]
actuator alarm *
[24]
24V power failure
[
rr
]
motor running
[UA]
Valve alarm*
[Ht]
thermostat tripped
[CA]
Control alarm*
[
r
P]
relay parity
The S contact form can be set normally
open
[no]
or normally closed
[nc]
.
The procedures for setting up contacts
S2, S3 and S4 are the same as those
shown for S1.
Unless specified with order, the
default settings for indication
contacts are as follows:
S1 – [CL] closed end position [no]
S2 – [OP] open end position [no]
S3 – [CL] closed end position [nc]
S4 . [OP] open end position [nc]
* Contact alarm indication will operate
under the same conditions as the
display alarm indication icons
(refer to
page 5 for information)
.
Using the
+
or
-
key display the desired
function.
PRESS THE
KEY.
The displayed function will flash
indicating that it has been set.
Contact S1 Configured to Trip
at Valve Closed Limit
PRESS THE
O
KEY.
When the S contact function is set to
[P0]
, the required intermediate position
value must be set.
No other contact function requires
a value to be set.
The value can be set from 1% open to
99% open in 1% increments.
Using the
+
or
-
key, display the
required value.
PRESS THE
KEY.
The displayed value will flash indicating
that it has been set.
Value Set to Indicate
25% Open
PRESS THE
O
KEY.
28
9.2
Indication Contacts
S1, S2, S3 and S4