With
[AA]
displayed
Use the
+
and
-
key to select the
required actuator operating time. The
settings are displayed in hexadecimal
and can be related to the actuator
speed as shown in Fig 8.2.
PRESS THE
KEY.
The displayed value will flash, indicating
that it has been set.
All speed settings are adjustable in unit
increments of hexadecimal. Any value
of hex outside of the range stated will
not be accepted into the actuator
memory.
% Speed
Hex Setting
25
19
30
1E
35
23
40
28
45
2D
50
32
55
37
60
3C
65
41
70
46
75
4B
80
50
85
55
90
5A
95
5F
100
64
Fig 8.2
NOTE:
Mains power has to be on
for speed setting to be carried out.
23
Speed Setting
AA
Positional Display
Q
Q
P?
O
PC
O
Ir
O
Ic
Q
Contact Function
cr
O
Contact S1
r1
Q
Contact S2
r2
Q
Contact S3
r3
Q
Contact S4
r4
Q
ESD Action
Control Mode
Configuration
A1
Q
Extra Indication
Folomatic
Remote
Bus
Contacts
CPT
Remote Control
Control Source
System
Option Selection
OE
O
OI
O
OF
O
Od
O
OP
[On]
Q
PA
Q
50
IQT operating time can be adjusted
between 25% and 100% of the
maximum time (50% and 100% for
IQT2000). IQT are factory set at the
maximum speed. IQTM actuators are
dispatched with the minimum speed set.
To access speed setting
[AA]
screen, bus
system
[OP]
has to be set to
[O
n
]
, using
the
+
and
-
key.
After this setting, proceed to screen
[AA]
.
IrDA
comms
Primary
Functions
IQT Speed
Setting
AA
Q