The default setting for ESD Override
Interlocks is
[OF]
. ESD action will not
override an active interlock applied to
the actuator.
If an applied ESD signal is required to
override active interlocks causing the
ESD action as set for A1, press the
+
or
-
key. The display will change to
[O
n
]
.
PRESS THE
KEY.
The displayed option will flash
indicating that it has been set.
ESD Override Interlock – Off
The default setting for ESD Override
Local Stop is
[OF]
. ESD will not override
local stop when selected.
If an applied ESD signal is required to
override local stop causing the ESD
action as set for A1, press the
+
or
-
key. The display will change to
[O
n
]
.
PRESS THE
KEY.
The displayed option will flash
indicating that it has been set.
ESD Override Local Stop – Off
The default setting for Local Actuator
Pushbutton control is self-maintained
[O
n
]
.
If non-maintained actuator pushbutton
control is required (jogging, inching,
push to run), press the
+
or
-
key. The
display will change to
[OF]
.
PRESS THE
KEY.
The displayed option will flash
indicating that it has been set.
Self-Maintained Local Control
The default setting for 2-wire Remote
Control is Stayput
[SP]
. If a open and
closed remote control signal are applied
simultaneously the actuator will stayput
(stop if running). Refer to actuator
wiring diagram or publication E120E.
Use the
+
or
-
key to select the
required priority:
[OP]
Open
[SP]
Stay put
[CL]
Close
PRESS THE
KEY.
The displayed option will flash
indicating that it has been set.
2-wire Control – Stayput Priority
31
A4
ESD Override
Interlocks
A5
ESD Override
Local Stop
A6
Maintained
Local Control
A7
2-wire Remote
Control