LCAC R32 Series
61
Service manual
PART 4. INSTALLATION
3.2.3 Hang indoor unit
1. Please refer to the upper data to locate the four positioning screw bolt hole on the ceiling. Be sure to mark the
areas where ceiling hook holes will be drilled.
2. Install and fit pipes and wires after you have finished installing the main body. When choosing where to start,
determine the direction of the pipes to be drawn out. Especially in cases where there is a ceiling involved, align
the refrigerant pipes, drain pipes, and indoor and outdoor lines with their connection points before mounting
the unit.
3. Install hanging screw bolts.
• Cut off the roof beam.
• Strengthen the place that has been cut off, and consolidate the roof beam.
4. After you select an installation location, align the refrigerant pipes, drain pipes, as well as indoor and outdoor
wires with their connection points before mounting the unit.
5. Drill 4 holes 10cm (4”) deep at the ceiling hook positions in the internal ceiling. Be sure to hold the drill at a 90°
angle to the ceiling.
6. Secure the bolt using the washers and nuts provided.
7. Install the four suspension bolts.
8. Mount the indoor unit with at least two people to lift and secure it. Insert suspension bolts into the unit’s hanging
holes. Fasten them using the washers and nuts provided.
9. Mount the indoor unit onto the hanging screw bolts with a block. Position the indoor unit flat using a level
indicator to prevent leaks
NOTE:
Confirm the minimum drain tilt is 1/100 or more.
Summary of Contents for J100Wi
Page 1: ...LCAC R32 SERIES Tenji W Jato W Nevo W ENG Service manual ...
Page 13: ...LCAC R32 Series 13 Service manual PART 2 INDOOR UNITS 1 5 2 Units 30 42K a Cooling b Heating ...
Page 14: ...LCAC R32 Series 14 Service manual PART 2 INDOOR UNITS 1 5 3 Units 48 55K a Cooling b Heating ...
Page 18: ...LCAC R32 Series 18 Service manual PART 2 INDOOR UNITS 1 10 1 Wiring diagram for T140Wi T160Wi ...
Page 44: ...LCAC R32 Series 44 Service manual PART 2 INDOOR UNITS 3 10 FIELD WIRING ...
Page 131: ...LCAC R32 Series 131 Service manual NOTES ...
Page 132: ...www rotenso pl email info rotenso pl Installer stamp ...