LCAC R32 Series
117
Service manual
4.4.19 J8 malfunction
Malfunction conditions
An abnormal voltage rise or drop is detected by checking the specified voltage detection circuit.
Possible causes
• Abnormal power supply
• Wiring mistake
• Faulty bridge rectifier
• Faulty IPM board
AC power input voltage
protection
J8 display
Check whether the power
voltage is normal.
Measure whether outdoor
terminal voltage is normal?
Restart the unit when the power
supply gets normal
No
Yes
No
Reconnect it well
Yes
Yes
No
Replace the IPM board, If the IPM board
and main board is in a board, replace the
outdoor main PCB
Yes
Replace the PFC module (If has)
No
Yes
Measure whether the voltage
between L and N is normal?
Yes
Measure whether input voltage
of bridge rectifier is normal?
Yes
No
No
Measure whether the voltage
between P and N is normal
refer to the Appendix 3?
Replace the bridge
rectifier
No
Check whether
bridge rectifier is
normal
Check the wiring of
reactor or inductance
Reconnect the
wiring
No
Check whether reactor
or inductance is normal
Yes
Replace reactor or
inductance
No
Check the wiring of
power wires well or
correctly
Reconnect it well
Check the wiring of
L and N wellor
correctly
Reconnect it well
Check the wiring of
bridge rectifier well
or correctly
PART 6. TROUBLESHOOTING
Summary of Contents for J100Wi
Page 1: ...LCAC R32 SERIES Tenji W Jato W Nevo W ENG Service manual ...
Page 13: ...LCAC R32 Series 13 Service manual PART 2 INDOOR UNITS 1 5 2 Units 30 42K a Cooling b Heating ...
Page 14: ...LCAC R32 Series 14 Service manual PART 2 INDOOR UNITS 1 5 3 Units 48 55K a Cooling b Heating ...
Page 18: ...LCAC R32 Series 18 Service manual PART 2 INDOOR UNITS 1 10 1 Wiring diagram for T140Wi T160Wi ...
Page 44: ...LCAC R32 Series 44 Service manual PART 2 INDOOR UNITS 3 10 FIELD WIRING ...
Page 131: ...LCAC R32 Series 131 Service manual NOTES ...
Page 132: ...www rotenso pl email info rotenso pl Installer stamp ...