LCAC R32 Series
120
Service manual
PART 7. CAPACITY TABLES
1.4 Capacity tables for 48K
a) Cooling
TC:
Total Capacity;
SHC:
Sensible Heat Capacity;
PI:
Power Input
Indoor
Outdoor temperature (DB, °C)
20
25
30
35
40
DB
WB
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
°C
°C
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
20
14
14,36
11,20
3,90
13,74
11,00
4,25
13,13
10,76
4,60
12,38
10,40
5,00
12,01
10,33
5,35
22
16
15,12
11,57
3,94
14,47
11,36
4,30
13,82
11,12
4,65
13,03
10,75
5,05
12,64
10,68
5,41
25
18
15,92
11,94
3,98
15,23
11,73
4,34
14,54
11,49
4,70
13,72
11,11
5,10
13,31
11,05
5,46
27
19
16,24
12,02
4,00
15,54
11,81
4,36
14,84
11,58
4,72
14,00
11,20
5,13
13,58
11,14
5,49
30
22
17,38
12,60
4,04
16,63
12,39
4,40
15,88
12,15
4,77
14,98
11,77
5,18
14,53
11,70
5,54
32
24
18,03
12,89
4,06
17,25
12,68
4,43
16,47
12,44
4,79
15,54
12,04
5,21
15,07
11,98
5,57
b) Heating
TC:
Total Capacity;
PI:
Power Input
Indoor
Outdoor temperature (DB, °C)
-20
-15
-10
-7
-2
2
7
12
17
DB
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
°C
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
15
7,46
4,36
9,29
4,85
10,84
5,09
11,77
5,24
12,60
5,32
13,27
5,39
16,58
4,90
16,09
4,56
15,42
4,41
18
7,35
4,43
9,15
4,92
10,68
5,17
11,60
5,32
12,42
5,41
13,07
5,47
16,34
4,97
15,85
4,63
15,20
4,48
20
7,25
4,49
9,02
5,00
10,53
5,25
11,43
5,40
12,24
5,49
12,88
5,56
16,10
5,05
15,62
4,70
14,97
4,55
22
7,10
4,54
8,84
5,05
10,31
5,30
11,20
5,46
11,99
5,54
12,62
5,61
15,78
5,10
15,30
4,74
14,67
4,59
24
7,03
4,58
8,75
5,10
10,21
5,36
11,09
5,51
11,87
5,60
12,49
5,67
15,62
5,15
15,15
4,79
14,52
4,64
25
6,96
4,61
8,66
5,12
10,10
5,38
10,97
5,54
11,75
5,62
12,36
5,69
15,46
5,18
14,99
4,81
14,37
4,66
27
6,88
4,65
8,57
5,17
10,00
5,44
10,86
5,59
11,62
5,68
12,24
5,75
15,30
5,23
14,84
4,86
14,22
4,70
1.5 Capacity tables for 55K
a) Cooling
TC:
Total Capacity;
SHC:
Sensible Heat Capacity;
PI:
Power Input
Indoor
Outdoor temperature (DB, °C)
20
25
30
35
40
DB
WB
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
°C
°C
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
20
14
16,11
12,56
4,52
15,41
12,33
4,93
14,72
12,07
5,34
13,89
11,66
5,80
13,47
11,58
6,21
22
16
16,96
12,97
4,57
16,22
12,74
4,98
15,49
12,47
5,39
14,62
12,06
5,86
14,18
11,98
6,27
25
18
17,85
13,39
4,62
17,08
13,15
5,03
16,31
12,88
5,45
15,39
12,46
5,92
14,92
12,39
6,33
27
19
18,21
13,48
4,64
17,43
13,24
5,06
16,64
12,98
5,47
15,70
12,56
5,95
15,23
12,49
6,37
30
22
19,49
14,13
4,69
18,65
13,89
5,11
17,81
13,62
5,53
16,80
13,20
6,01
16,30
13,12
6,43
32
24
20,22
14,45
4,71
19,34
14,22
5,13
18,47
13,95
5,56
17,43
13,51
6,04
16,90
13,44
6,46
Summary of Contents for J100Wi
Page 1: ...LCAC R32 SERIES Tenji W Jato W Nevo W ENG Service manual ...
Page 13: ...LCAC R32 Series 13 Service manual PART 2 INDOOR UNITS 1 5 2 Units 30 42K a Cooling b Heating ...
Page 14: ...LCAC R32 Series 14 Service manual PART 2 INDOOR UNITS 1 5 3 Units 48 55K a Cooling b Heating ...
Page 18: ...LCAC R32 Series 18 Service manual PART 2 INDOOR UNITS 1 10 1 Wiring diagram for T140Wi T160Wi ...
Page 44: ...LCAC R32 Series 44 Service manual PART 2 INDOOR UNITS 3 10 FIELD WIRING ...
Page 131: ...LCAC R32 Series 131 Service manual NOTES ...
Page 132: ...www rotenso pl email info rotenso pl Installer stamp ...