LCAC R32 Series
118
Service manual
1. TENJI - SUPER SLIM CASSETTE
1.1 Capacity tables for 18K
a) Cooling
TC:
Total Capacity;
SHC:
Sensible Heat Capacity;
PI:
Power Input
PART 7. CAPACITY TABLES
Indoor
Outdoor temperature (DB, °C)
20
25
30
35
40
DB
WB
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
°C
°C
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
20
14
5,44
4,24
1,25
5,20
4,16
1,36
4,97
4,07
1,47
4,69
3,94
1,60
4,55
3,91
1,71
22
16
5,72
4,38
1,26
5,48
4,30
1,37
5,23
4,21
1,49
4,93
4,07
1,62
4,79
4,04
1,73
25
18
6,03
4,52
1,27
5,77
4,44
1,39
5,51
4,35
1,50
5,19
4,21
1,63
5,04
4,18
1,75
27
19
6,15
4,55
1,28
5,88
4,47
1,39
5,62
4,38
1,51
5,30
4,24
1,64
5,14
4,22
1,75
30
22
6,58
4,77
1,29
6,29
4,69
1,41
6,01
4,60
1,52
5,67
4,46
1,66
5,50
4,43
1,77
32
24
6,82
4,88
1,30
6,53
4,80
1,41
6,24
4,71
1,53
5,88
4,56
1,66
5,71
4,54
1,78
b) Heating
TC:
Total Capacity;
PI:
Power Input
Indoor
Outdoor temperature (DB, °C)
-20
-15
-10
-7
-2
2
7
12
17
DB
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
°C
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
15
2,87
1,35
3,10
1,34
3,33
1,31
3,50
1,29
3,85
1,27
4,13
1,25
5,74
1,46
5,56
1,35
5,34
1,31
18
2,83
1,37
3,05
1,36
3,28
1,33
3,45
1,31
3,79
1,29
4,07
1,27
5,65
1,48
5,48
1,37
5,26
1,33
20
2,79
1,40
3,01
1,38
3,23
1,35
3,40
1,34
3,74
1,31
4,01
1,29
5,57
1,50
5,40
1,40
5,18
1,35
22
2,73
1,41
2,95
1,39
3,17
1,36
3,33
1,35
3,66
1,32
3,93
1,30
5,46
1,52
5,29
1,41
5,08
1,36
24
2,70
1,42
2,92
1,41
3,13
1,38
3,30
1,36
3,63
1,34
3,89
1,32
5,40
1,53
5,24
1,42
5,02
1,38
25
2,67
1,43
2,89
1,41
3,10
1,38
3,26
1,37
3,59
1,34
3,85
1,32
5,35
1,54
5,19
1,43
4,97
1,38
27
2,65
1,44
2,86
1,43
3,07
1,40
3,23
1,38
3,55
1,36
3,81
1,34
5,29
1,55
5,13
1,44
4,92
1,40
1.2 Capacity tables for 24K
a) Cooling
TC:
Total Capacity;
SHC:
Sensible Heat Capacity;
PI:
Power Input
Indoor
Outdoor temperature (DB, °C)
20
25
30
35
40
DB
WB
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
°C
°C
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
20
14
7,18
5,60
1,67
6,87
5,50
1,81
6,56
5,38
1,96
6,19
5,20
2,14
6,01
5,16
2,28
22
16
7,56
5,78
1,68
7,23
5,68
1,83
6,91
5,56
1,98
6,52
5,38
2,16
6,32
5,34
2,31
25
18
7,96
5,97
1,70
7,61
5,86
1,85
7,27
5,74
2,00
6,86
5,56
2,18
6,65
5,52
2,33
27
19
8,12
6,01
1,71
7,77
5,91
1,86
7,42
5,79
2,01
7,00
5,60
2,19
6,79
5,57
2,34
30
22
8,69
6,30
1,73
8,31
6,19
1,88
7,94
6,07
2,03
7,49
5,89
2,21
7,27
5,85
2,37
32
24
9,01
6,44
1,73
8,62
6,34
1,89
8,24
6,22
2,05
7,77
6,02
2,22
7,54
5,99
2,38
Summary of Contents for J100Wi
Page 1: ...LCAC R32 SERIES Tenji W Jato W Nevo W ENG Service manual ...
Page 13: ...LCAC R32 Series 13 Service manual PART 2 INDOOR UNITS 1 5 2 Units 30 42K a Cooling b Heating ...
Page 14: ...LCAC R32 Series 14 Service manual PART 2 INDOOR UNITS 1 5 3 Units 48 55K a Cooling b Heating ...
Page 18: ...LCAC R32 Series 18 Service manual PART 2 INDOOR UNITS 1 10 1 Wiring diagram for T140Wi T160Wi ...
Page 44: ...LCAC R32 Series 44 Service manual PART 2 INDOOR UNITS 3 10 FIELD WIRING ...
Page 131: ...LCAC R32 Series 131 Service manual NOTES ...
Page 132: ...www rotenso pl email info rotenso pl Installer stamp ...