LCAC R32 Series
113
Service manual
4.4.15 J3 Malfunction
Malfunction conditions
When the voltage signal that IPM send to compressor drive chip is abnormal, the display LED will
show “P6” and AC will turn off.
Possible causes
• Wiring mistake
• Faulty IPM board
• Faulty outdoor fan ass’y
• Compressor malfunction
• Faulty outdoor PCB
At first test the resistance between every two ports of U, V, W of IPM and P, N. If any result of them is 0 or close to 0,
the IPM is defective. Otherwise, please follow the procedure below:
J3 display
PFC module protection
Check whether the
connecting line between
main board and the PFC
module is connected tightly
Yes
Measure whether the voltage
between P and Nisnormal
referto the
Appendix
3?
No
Check
whether
the
inductance of PFC module
is good?If the inductanceis
good, the resistance of the
two ports is 0
Yes
Replace the inductance
No
Connect it tightly, check
normal or not
Replace the outdoor main board
Yes
Yes
No
No
Replace the PFC module
Trouble is solved
PART 6. TROUBLESHOOTING
Summary of Contents for J100Wi
Page 1: ...LCAC R32 SERIES Tenji W Jato W Nevo W ENG Service manual ...
Page 13: ...LCAC R32 Series 13 Service manual PART 2 INDOOR UNITS 1 5 2 Units 30 42K a Cooling b Heating ...
Page 14: ...LCAC R32 Series 14 Service manual PART 2 INDOOR UNITS 1 5 3 Units 48 55K a Cooling b Heating ...
Page 18: ...LCAC R32 Series 18 Service manual PART 2 INDOOR UNITS 1 10 1 Wiring diagram for T140Wi T160Wi ...
Page 44: ...LCAC R32 Series 44 Service manual PART 2 INDOOR UNITS 3 10 FIELD WIRING ...
Page 131: ...LCAC R32 Series 131 Service manual NOTES ...
Page 132: ...www rotenso pl email info rotenso pl Installer stamp ...