4.4.2 Compressor Speed Malfunction/ Zero Speed Protection / Synchronous Fault Protection
LED1(Green) off/LED2 (Red)flash
or LED1(Green) flash/LED2 (Red)on
Is there at least one LED in
the compressor driven chip
light?
Check the signal wire between
the compressor driven chip and
the compressor. Is it connected
properly?
Reconnect and retry. Is the
error still displayed?
Replace the outdoor main
PCB. Is the system running
normally?
Replace the compressor
No
No
Yes
No
Yes
Problem is resolved
No
Yes
Yes
4.4.3 MCE Malfunction
Yes
Replace the outdoor main
PCB
Power off, then restart the
unit 2 minutes later. Does a
probllem stiilll exiist?
MCE mallfunctiion
PART 6. TROUBLESHOOTING