LCAC R32 Series
17
Service manual
2.9 THE SPECIFICATION OF POWER
PART 2. INDOOR UNITS
Model(Btu/h)
18000~24000
36000
36000
48000~60000
Indoor power
Phase
1-phase
1-phase
1-phase
-
Frequency and Voltage
220-240V, 50Hz
220-240V, 50Hz
220-240V, 50Hz
-
Power wiring (mm
2
)
3×1.0
3×1.0
3×1.0
-
Circuit breaker/Fuse (A)
15/10
15/10
15/10
-
Indoor power
Phase
1-phase
1-phase
3-phase
3-phase
Frequency and Voltage
220-240V, 50Hz
220-240V, 50Hz
380-415V, 50Hz
380-415V, 50Hz
Power wiring (mm
2
)
3×2.5
3×4.0
5×2.5
5×2.5
Circuit breaker/Fuse (A)
25/20
40/30
25/20
30/25
Indoor/Outdoor Connecting Wiring
(Weak Electric Signal) (mm
2
)
2×0.2
2×0.2
2×0.2
2×0.2
Indoor/Outdoor Connecting Wiring
(Strong Electric Signal) (mm
2
)
-
-
-
3×1.0
1.10 FIELD WIRING
1.10.1 Wiring diagram for T50Wi, T70Wi, T100Wi