LCAC R32 Series
30
Service manual
PART 2. INDOOR UNITS
2.8 ACCESSORIES
Item
Qty
Shape
Usage category
Soundproof / insulation sheath
2
Tubing & Fittings
Drain joint
1
Drainpipe Fittings
(for cooling & heating)
Seal ring
1
Magnetic ring
(twist the electric wires L and N
around the magnetic ring to five
circles)
1
EMC & It’s Fitting (for some models)
Wired controller
1
Wired controller & Its Frame
Owner’s manual of wired controller
1
Wired controller installation manual
1
Owner’s manual
1
Others
Installation manual
1
Connecting wire for display (2m)
1 (on some
models)
-
Cord protection rubber ring
1 (on some
models)
2.9 THE SPECIFICATION OF POWER
Model (Btu/h)
18000~24000
36000
Power
Phase
1-phase
1-phase
Frequency and Voltage
220-240V, 50Hz
220-240V, 50Hz
Power wiring (mm
2
)
3×2.5
3×4.0
Circuit breaker/Fuse (A)
30/20
40/30
Indoor/Outdoor Connecting Wiring
(Weak Electric Signal) (mm
2
)
2×0.2
2×0.2
Indoor/Outdoor Connecting Wiring
(Strong Electric Signal) (mm
2
)
3×1.0
3×1.0
Model (Btu/h)
36000
48000~60000
Power
Phase
3-phase
3-phase
Frequency and Voltage
380-415V, 50Hz
380-415V, 50Hz
Power wiring (mm
2
)
5×2.5
5×2.5
Circuit breaker/Fuse (A)
30/20
30/25
Indoor/Outdoor Connecting Wiring
(Weak Electric Signal) (mm
2
)
2×0.2
2×0.2
Indoor/Outdoor Connecting Wiring
(Strong Electric Signal) (mm
2
)
3×1.0
3×1.0
Summary of Contents for J100Wi
Page 1: ...LCAC R32 SERIES Tenji W Jato W Nevo W ENG Service manual ...
Page 13: ...LCAC R32 Series 13 Service manual PART 2 INDOOR UNITS 1 5 2 Units 30 42K a Cooling b Heating ...
Page 14: ...LCAC R32 Series 14 Service manual PART 2 INDOOR UNITS 1 5 3 Units 48 55K a Cooling b Heating ...
Page 18: ...LCAC R32 Series 18 Service manual PART 2 INDOOR UNITS 1 10 1 Wiring diagram for T140Wi T160Wi ...
Page 44: ...LCAC R32 Series 44 Service manual PART 2 INDOOR UNITS 3 10 FIELD WIRING ...
Page 131: ...LCAC R32 Series 131 Service manual NOTES ...
Page 132: ...www rotenso pl email info rotenso pl Installer stamp ...