B-4
Parameter Information
Table B.1 (cont.) Parameter List
①
Read-only capability.
②
The scale factor is 100 when Motor FLC, parameter 70, has a programmed value of up to 10.0 Amps; above 10.0 Amps, the scale factor is 10.
Group
Parameter
Description
Parameter
Number
Display
Units
Scale
Factor
Minimum
Maximum
Default
Setting
User
Setting
Calibrate
Overload
Class
36
—
—
Off, 10, 15, 20, and 30
Off
Overload
Reset
88
—
—
Manual-Auto
Manual
Motor HP
Rating
79
HP
10
0.0
6,553.5
0.0
Motor kW
Rating
80
kW
10
0.0
6,553.5
0.0
Line Voltage
69
Volts
1
0
9999
480
Motor FLC
70
Amps
10
1.0
999.9
1.0
Service
Factor
84
—
100
0.01
1.99
1.15
Motor Code
Letter
72
—
—
A, B, C, D, E, F, G, H, J, K, L,
M, N, P, R, S, T, U, and V
G
LRC Ratio
81
—
10
0.0
19.9
0.0
Converter
Rating
74
—
—
None, 20, 180, 630
None
CT Ratio
75
—
—
5, 50, 75, 100, 150, 200,
250, 300, 400, 500, 600, 750,
800, 1000, 1200 :5
5:5
Calibration
76
—
—
Off, Activate
Off
Enter Calib.
Amps
77
Amps
②
0.01
999.9
0.0
Current
Phase A
①
4
Amps
10
—
—
—
Parameter
Mgmt.
17
—
—
Ready, Default Init.
Recll Frm EE,Store In EE
Ready
Summary of Contents for SMC Dialog Plus
Page 46: ...2 20 Installation ...
Page 78: ...4 14 Programming ...
Page 149: ...9 6 Diagnostics ...
Page 157: ...10 8 Troubleshooting Figure 10 3 Removal of Control Module 180 360A 1 3 2 4 ...
Page 169: ...A 6 Specifications ...
Page 179: ...C 4 Renewal Parts ...