Wiring
3-5
Fan Power
Controllers rated 97A
–
1000A have heatsink fan(s). Refer to Table 3.D
for the control power VA requirements of the heatsink fans.
Fan Terminations
See Figure 3.2 to Figure 3.4 for fan power connection locations.
Figure 3.6 97A and 135A Fan Terminations
Figure 3.7 180A to 500A Fan Terminations
Figure 3.8 650A to 1000A Fan Terminations
!
ATTENTION:
The fan jumpers have been factory
installed for 110/120 VAC input. Refer to Figure 3.6
through Figure 3.8 for 220/240 VAC fan wiring. Note
that 220/240 VAC fan wiring is not available for the
650A–1000A controllers. After wiring for the 97A and
135A controllers is complete, replace control terminal
strip cover.
Factory Set
110/120 VAC
Optional
220/240 VAC
Jumpers
To
Supply
Jumper
To
Supply
1
2
3
4
1
2
3
4
Factory Set
110/120 VAC
Optional
220/240 VAC
To
Supply
To
Supply
Jumpers Jumper
1 2 3 4 5
1 2 3 4 5
Factory Set
110/120 VAC
To
Supply
1 2 3 4 5 6
Note: 220/240 VAC is not available.