Options
7-3
Programming Parameters
The following table provides the option-specific parameters that are
provided with each control option. These parameters are in addition
to those already discussed in the Basic Setup, Advanced Setup,
Metering, and Calibration groups. Diagrams supporting the options
described below are shown later in this chapter.
Option
Parameter
Range
Soft Stop
SMC Option
This parameter identifies the type of
control present and is not user
programmable.
Soft Stop
Soft Stop Time
Allows the user to set the time
period for the soft stopping function.
0–60 seconds
Pump Control
SMC Option
This parameter identifies the type of
control present and is not user
programmable.
Pump Control
Pump Stop Time
Allows the user to set the time
period for the pump stopping
function.
0–120 seconds
Starting Mode
Allows the user to program the SMC
Dialog Plus controller for the type of
starting that best fits the application.
Pump Start, Soft Start,
Current Limit Start
Preset Slow
Speed
SMC Option
This parameter identifies the type of
control present and is not user
programmable.
Preset Slow
Slow Speed Select
Allows the user to program the slow
speed that best fits the application.
Low: 7% – forward,
10% – reverse
High: 15% – forward,
20% – reverse
Slow Speed Direction
This parameter programs the slow
speed motor rotational direction.
Forward, Reverse
Slow Accel Current
Allows the user to program the
required current to accelerate the
motor to slow speed operation.
0–450% of full load
current
Slow Running Current
Allows the user to program the
required current to operate the
motor at the slow speed setting.
0–450% of full load
current