2-2
Installation
General Precautions
In addition to the precautions listed throughout this manual, the
following statements, which are general to the system, must be read
and understood.
Heat Dissipation
The following table provides the maximum heat dissipation at rated
current for the controllers. For currents lower than rated value, heat
dissipation will be reduced.
Table 2.A Maximum Heat Dissipation
Enclosures
The open-style design of the SMC Dialog Plus controller requires that
it be installed in an enclosure.
The internal temperature of the
enclosure must be kept within the range of 0°C to 50°C.
!
ATTENTION:
The controller contains ESD
(electrostatic discharge) sensitive parts and assemblies.
Static control precautions are required when installing,
testing, servicing, or repairing the assembly.
Component damage may result if ESD control
procedures are not followed. If you are not familiar with
static control procedures, refer to applicable ESD
protection handbooks.
!
ATTENTION:
An incorrectly applied or installed
controller can damage components or reduce product
life. Wiring or application errors, such as undersizing
the motor, incorrect or inadequate AC supply, or
excessive ambient temperatures, may result in
malfunction of the system.
!
ATTENTION:
Only personnel familiar with the
controller and associated machinery should plan or
implement the installation, start-up, and subsequent
maintenance of the system. Failure to do this may result
in personal injury and/or equipment damage.
SMC Rating
24A
35A
54A
97A
135A
180A
240A
360A
500A
650A
720A
850A
1000A
Max. Watts
110
150
200
285
410
660
935
1170
1400
2025
2250
2400
2760