3-6
Wiring
Control Terminal
Designations
As shown in Figure 3.9, the SMC Dialog Plus controller contains 20
control terminals on the front of the controller.
Figure 3.9 SMC Dialog Plus Controller Control Terminals
①
Do not connect any additional loads to these terminals. These “parasitic” loads may cause problems with operation, which may result in false starting and stopping.
②
When control power is absent from terminals 11 and 12, this contact will be normally open. Upon application of control power, the contact will take the state, normally
open or normally closed, as programmed.
Grounding
Provision
Provision for connecting a field installed grounding conductor is
provided on each controller. It is shown in Figure 3.10 and is located
on the heatsink. This symbol is the ground connection identification
symbol as defined by IEC Publication 417, Symbol 5019.
If the protective conductor is not connected to the heatsink, the
plating and/or paint must be cleaned from the four mounting holes or
four star washers (tooth lock washers) must be used.
Figure 3.10 Grounding Provision
Terminal
Number
Description
Terminal
Number
Description
11
Control Power Input
21
Not Used
12
Control Power Common
22
Not Used
13
Controller Enable Input
①
23
Not Used
14
Logic Ground
24
Not Used
15
Dual Ramp/Option Input
①
25
Converter Module Fanning Strip Connection
②
16
Start Input
①
26
Converter Module Fanning Strip Connection
②
17
Stop Input
①
27
Converter Module Fanning Strip Connection
②
18
Auxiliary Relay Common
28
Converter Module Fanning Strip Connection
②
19
N.O. Auxiliary Contact #1 (Normal/Up-to-speed)
29
N.O./N.C. Auxiliary Contact #3 (Normal/Fault)
20
N.C. Auxiliary Contact #2 (Normal/Up-to-speed)
30
N.O./N.C. Auxiliary Contact #3 (Normal/Fault)
11
21
12
22
13
23
14
24
15
25
16
26
17
27
18
28
19
29
20
30