5-4
Calibration
Calibration Procedure (cont.)
Description
Action
Display
7.
You can scroll to the next
parameter to view the current
measurement in phase A.
8.
Scroll to the next parameter to
save the Calibrate group
settings.
9.
Press the Select key. Scroll
with the Up/Down keys to Store
In EE selection. Press the Enter
key to save the settings to
EEPROM.
!
ATTENTION:
After calibration is completed,
program the desired overload class and save the setting
to the controller’s EEPROM.
!
ATTENTION:
This method of current measurement
is not applicable to multi-motor installations or resistive
heating loads. Utilization of the Bulletin 825 converter
module is required for these applications if current
measurement is required.
CURRENT PHASE A
###.# AMPS
PARAMETER MGMT
READY
PARAMETER MGMT
STORE IN EE