58
Publication 1747-SG001D-EN-P — January 2009
Communication
Cables
The following tables provide a description of available communication cables and a
summary of cable connectivity.
Communication Cables
Cat. No.
Description
1761-CBL-AC00
SLC 5/03, 5/04, and 5/05 Communication Cable - This 45 cm (17.7 in) cable has two 9-pin DTE connectors and is used to connect the SLC 5/03, 5/04, or 5/05 processor RS-232
channel (channel 0) to port 1 of the 1761-NET-AIC.
1761-CBL-AP00
SLC 5/03, 5/04, and 5/05 Communication Cable - This 45 cm (17.7 in) cable has a 9-pin DTE and an 8-pin mini DIN connector and is used to connect the SLC 5/03, 5/04, or 5/05
processor RS-232 channel (channel 0) to port 2 of the 1761-NET-AIC.
1761-CBL-PM02
SLC 5/03, 5/04, and 5/05 Communication Cable - This 2 m (6.5 ft) cable has a 9-pin DTE and an 8-pin mini DIN connector and is used to connect the SLC 5/03, 5/04, or SLC 5/05
processor RS-232 channel (channel 0) to port 2 of the 1761-NET-AIC.
1761-CBL-AS03
RJ45 to 6-Pin Phoenix Connector Communication Cable - This 3 m (9.8 ft) cable is used to connect the SLC 5/01, SLC 5/02, and SLC 5/03 processor RJ45 port to port 3 of the 1761-
NET-AIC.
1761-CBLAS09
RJ45 to 6-Pin Phoenix Connector Communication Cable - This 9.5 m (31.2 ft) cable is used to connect the SLC 5/01, SLC 5/02, and SLC 5/03 processor RJ45 port to port 3 of the
1761-NET-AIC.
1747-CP3
SLC 5/03, 5/04, and 5/05 RS-232 Programmer Cable - This 3 m (10 ft) cable has two 9-pin DTE connectors and is used to connect the SLC processor RS-232 channel (channel 0) to
a personal computer serial port.
1747-C11
Processor to Isolated Link Coupler Replacement Cable – This 304.8 mm (12 in) cable is used to connect the SLC 500 processor to the Isolated Link Coupler (1747-AIC).
1747-C13
Specialty Module to Isolated Link Coupler Cable - Use a 1747-C13 cable to connect a BASIC or KE module to an Isolated Link Coupler (1747-AIC). Also connects 1747-UIC RS-485
port to AIC or SLC RJ45 port.
Cable Connectivity Summary
For Connectivity Between These Devices
Preferred Cable
Catalog Number
These Cables
May Be Used
1746-A4, -A7, -A10, or -A13 Chassis
1746-A4, -A7, -A10, or -A13 Chassis
1746-C7
1746-C9
1746-C16
⎯
1747-DTAM-E Data Table Access Module
SLC 500 Processors (DH-485 Channel)
1747-C10
1747-C11
1747-C20
1746-AIC Isolated Link Coupler
SLC 500 Processors (DH-485 Channel)
1747-C11
1747-C10
1747-C13
1747-C20
1747-UIC USB to DH-485 Interface Converter
1747-KE DH-485/RS-232C Interface Module
1746-BAS BASIC Module
1747-AIC Isolated Link Coupler (J2 Port)
SLC 500 Processors (DH-485 Channel)
1747-C13
1747-C10
1747-C11
1746-
xx
32 32-channel I/O Modules
1492-IFM40
x
1492-CABLE
x
H
⎯
SLC 5/03 Processor (RS-232 Channel 0)
SLC 5/04 Processor (RS-232 Channel 0)
SLC 5/05 Processor (RS-232 Channel 0)
Personal Computer Serial Port (9-Pin DTE)
1747-CP3
⎯
1746-I/O
1492-IFM
xx
Interface Modules
1492-CABLE
xx
⎯
1747-SN Remote I/O Scanner
1747-DCM Direct Communication Module
1747-ASB SLC Remote I/O Adapter Module
Remote I/O Network
Belden 9463
⎯
SLC 5/04 Processors (1747-L541, -542, -543)
Data Highway Plus
Belden 9463
⎯
1747-AIC Isolated Link Coupler
1761-NET-AIC Communication Interface
1784-PKTX(D) Communication Interface Card
1747-AIC Isolated Link Coupler
Belden 9842
Belden 3106A
⎯
1747-DPS1 and 1747-DPS2 Port Splitter
Rockwell Automation controllers, PanelView, PanelView
Plus, VersaView, InView and Personal Computers
Uses available 1747, 1756, 1761, 2706
and 2711 cables.
Refer to Installation Instructions for the
port splitter (1747-IN516).
www.aotewell.com
www.fa-market.com
AoteWell International.inc
Tel: +852-6563-2160