6-10
SP600 AC Drive User Manual
When using the braking resistor connections, parameter 163 (DB
Resistor Type) must be set to one of the following selections:
•
0 = Internal: Refers to DB plate-style resistor options kits that can
be mounted directly to the heatsink chassis of the drive (for
example, 6SP2-DB1-A).
•
1 = External: Refers to externally-mounted resistors. These
could be panel, cage, or other type of mounting, and are not
specifically designed by Rockwell Automation to mount directly to
the SP600 AC drive.
!
ATTENTION: AC drives do not offer protection for
externally mounted braking resistors. A risk of fire
exists if external braking resistors are not protected.
External resistor packages must be self-protected
from overtemperature, or the protective circuit
shown in figure 6.8, or an equivalent, must be
supplied.
ATTENTION: Equipment damage may result if a
drive-mounted (internal) resistor is installed and
parameter 163 is set to 1 (External Res). Thermal
protection for the internal resistor will be disabled,
resulting in possible device damage
Figure 6.8 – Protective Circuit for External Resistor Packages
Power On
R (L1)
S (L2)
T (L3)
Power Source
DB Resistor Thermostat
Power Off
M
M
(Input Contactor) M
Three-Phase
AC Input
AC Drive
Summary of Contents for Reliance electric 6SP201-015
Page 14: ...1 2 SP600 AC Drive User Manual ...
Page 54: ...Mounting the Drive 3 16 ...
Page 82: ...6 12 SP600 AC Drive User Manual ...
Page 96: ...7 14 SP600 AC Drive User Manual ...
Page 232: ...Parameter Descriptions 12 102 ...
Page 280: ...B 8 SP600 AC Drive User Manual ...
Page 282: ...C 2 SP600 AC Drive User Manual ...
Page 284: ...D 2 SP600 AC Drive User Manual ...
Page 298: ......
Page 299: ......