![Rockwell Automation Reliance electric 6SP201-015 User Manual Download Page 235](http://html.mh-extra.com/html/rockwell-automation/reliance-electric-6sp201-015/reliance-electric-6sp201-015_user-manual_1475508235.webp)
Troubleshooting the Drive
13-3
13.2
Determining Drive Status Using the Ready LED
*Network status LEDs are not available unless a network communications
module is installed in the drive. Refer to the appropriate network module
manual for these status LED definitions.
Figure 13.2 – Location of the Ready LED
Front View
Ready LED
See table 12.1
Table 13.1 – Ready LED Status Definitions
Color
State
Description
Green
Flashing
Drive ready, but not running and no faults
are present.
Steady
Drive running, no faults are present.
Yellow
See section
13.3.
Flashing
The drive is not ready. Check parameter
214 (Start Inhibits).
Steady
An alarm condition exists.
Check parameters 211 (Drive Alarm 1)
and 212 (Drive Alarm 2).
Red
See section
13.4.
Flashing
A fault has occurred.
Steady
A non-resettable fault has occurred.
Network
Status
LEDs*