Parameter Descriptions
12-25
Analog input reference scaling. Scales the lower value of the Speed
Ref A Sel (90) selection when the source is an analog input.
Important:
Parameter 92 corresponds to Analog In 1 Lo (323) or
Analog In 2 Lo (326) depending on the analog input
assigned as a source. See figure 12.51.
Specifies the manual speed reference source when a digital input is
configured for manual mode selection. See parameters 361-366.
Analog input reference scaling. Scales the upper value of the TB
Man Ref Sel (96) selection when the source is an analog input.
Parameter 97 should be set in conjunction with Analog In 1 Hi (322)
or Analog In 2 Hi (325) depending on the appropriate analog input
used. See figure 12.51.
92
Speed Ref A Lo
Range:
-/+ Maximum Speed [0.1 Hz]
Default:
0.0 Hz
Access:
1
Path: Speed Command>Speed References
See also:
81
96
TB Man Ref Sel
Range:
1 = Analog In 1
2 = Analog In 2
3-8 = Reserved
9 = MOP Level
10 = Reserved
11 = Preset Spd 1
12 = Preset Spd 2
13 = Preset Spd 3
14 = Preset Spd 4
15 = Preset Spd 5
16 = Preset Spd 6
17 = Preset Spd 7
Default:
2 = Analog In 2
Access:
1
Path: Speed Command>Speed References
See also:
97, 98, 361-366
97
TB Man Ref Hi
Range:
-/+ Maximum Speed [0.1 Hz]
Default:
Maximum Speed
Access:
1
Path: Speed Command>Speed References
See also:
96
Summary of Contents for Reliance electric 6SP201-015
Page 14: ...1 2 SP600 AC Drive User Manual ...
Page 54: ...Mounting the Drive 3 16 ...
Page 82: ...6 12 SP600 AC Drive User Manual ...
Page 96: ...7 14 SP600 AC Drive User Manual ...
Page 232: ...Parameter Descriptions 12 102 ...
Page 280: ...B 8 SP600 AC Drive User Manual ...
Page 282: ...C 2 SP600 AC Drive User Manual ...
Page 284: ...D 2 SP600 AC Drive User Manual ...
Page 298: ......
Page 299: ......