Parameter Descriptions
12-101
Sets the off delay time for the digital outputs. This is the time
between the disappearance of a condition and de-activation of the
relay.
387
Dig Out2 OffTime
Range:
0.00 to 600.00 Sec [0.01 Sec]
Default:
0.00 Sec
Access:
2
Path: Inputs & Output>Digital Outputs
See also:
384
Figure 12.54 – Dig Out2 OffTime (387)
Comparator
Delay
Timer
Output
Frequency
(384)
Dig Out2
Level (385)
Dig Out2
OnTime
(386)
Relay Out2
(Term 24, 25, 26)
Dig Out2
OffTime
(387)