10-6
SP600 AC Drive User Manual
10.3.4 Speed Reference Source
The default configuration is for keypad reference source. If you want
to use an analog reference input for control, you must configure the
analog reference inputs. The example below shows speed
reference from an analog voltage input. Analog inputs can also be
configured for 4 to 20 mA.
Figure 10.4 – Two-Wire and Three-Wire Start/Stop Control
3
7
8
9
Lo
gic C
om.
S
uppl
y C
om
.
R
un
Fu
nctio
n
Lo
ss
+24
V
D
C
2
Two-Wire Start/Stop Control
Three-Wire Start/Stop Control
(89) Logic Source Sel = Terminal Block
(361) Digital In1 Sel = Not Used
(362) Digital In2 Sel = Run
(363) Digital In3 Sel = Function Loss
(361) Digital In1 Sel = Stop
(362) Digital In2 Sel = Start
(363) Digital In3 Sel = Function Loss
(89) Logic Source Sel = Terminal Block
Lo
gic
Co
m.
Sup
pl
y
C
om
.
St
ar
t
Fu
nc
tio
n
Lo
ss
+2
4 VDC
St
op
1
2
3
7
8
9
Figure 10.5 – Analog Speed Reference
10
15
Anal
og In
1
(-
)
C
om
mon
+10 V
D
C
An
al
og
In
1
(+)
14
22
Analog Reference Wiring (Voltage)
(90) Speed Ref A Sel = Analog In1
(91) Speed Ref Hi = 60 Hz
(92) Speed Ref Lo = 0 Hz
(P320) Analog In Config =..xx00
(P322) Analog In Hi = 10.0 V
(P323) Analog In Lo = 0.0 V
Summary of Contents for Reliance electric 6SP201-015
Page 14: ...1 2 SP600 AC Drive User Manual ...
Page 54: ...Mounting the Drive 3 16 ...
Page 82: ...6 12 SP600 AC Drive User Manual ...
Page 96: ...7 14 SP600 AC Drive User Manual ...
Page 232: ...Parameter Descriptions 12 102 ...
Page 280: ...B 8 SP600 AC Drive User Manual ...
Page 282: ...C 2 SP600 AC Drive User Manual ...
Page 284: ...D 2 SP600 AC Drive User Manual ...
Page 298: ......
Page 299: ......