![Rockwell Automation Reliance electric 6SP201-015 User Manual Download Page 202](http://html.mh-extra.com/html/rockwell-automation/reliance-electric-6sp201-015/reliance-electric-6sp201-015_user-manual_1475508202.webp)
12-72
SP600 AC Drive User Manual
Displays elapsed hours since initial drive power up. This value will
roll over to 0 after the drive has been powered on for more than the
maximum value shown.
Selects alarm conditions that will initiate a drive alarm.
See table 12.3 for alarm descriptions.
242
Power Up Marker
Range:
0.0000 to 4,294,967.2925 Hr [0.0001 Hr]
Default:
Read Only
Access:
2
Path: Utility>Faults
See also:
244, 246, 248, 250
32
259
Alarm Config 1
Range:
See figure12.42
Default:
See figure12.42
Access:
2
Path: Utility>Alarms
See also:
Figure 12.42 – Alarm Config 1 (259)
1 1
1
x
x
x
x
x
x
10
0
1
2
3
4
5
6
7
8
9
11
12
13
14
15
1 =Enabled
0 =Disabled
x =Reserved
Bit #
Factory Default Bit Values
UnderV
oltage
Po
w
er Loss
Decel Inhibit
Nibble 1
Nibble 2
Nibble 3
Nibble 4
x
x
1
Prechrg Actv
Anlg in Loss
IntDBRes OH
Dr
v OL Lvl 1
Dr
v OL Lvl 2
1
1
1 1
Summary of Contents for Reliance electric 6SP201-015
Page 14: ...1 2 SP600 AC Drive User Manual ...
Page 54: ...Mounting the Drive 3 16 ...
Page 82: ...6 12 SP600 AC Drive User Manual ...
Page 96: ...7 14 SP600 AC Drive User Manual ...
Page 232: ...Parameter Descriptions 12 102 ...
Page 280: ...B 8 SP600 AC Drive User Manual ...
Page 282: ...C 2 SP600 AC Drive User Manual ...
Page 284: ...D 2 SP600 AC Drive User Manual ...
Page 298: ......
Page 299: ......