Parameter Descriptions
12-7
Displays the setpoint value of the signal at the MOP
(Motor-Operated Potentiometer) function. The setpoint can be
retained after power down or stop by setting parameter 194.
Displays the present DC bus voltage level.
Displays a six-minute average of the DC bus voltage level.
Displays the value of the signal at the analog inputs. This value
does not include user-programmed scaling information (for
example, Analog In1 Hi). The value displayed depends on the
setting of Analog In Config (320).
11
MOP Frequency
Range:
+/- 400.0 [0.1 Hz]
Default:
Read Only
Access:
1
Path: Monitor>Metering
See also:
194, 195
12
DC Bus Voltage
Range:
Voltage rating-dependent [0.1 VDC]
Default:
Read Only
Access:
1
Path: Monitor>Metering
See also:
13
DC Bus Memory
Range:
Voltage rating-dependent [0.1 VDC]
Default:
Read Only
Access:
2
Path: Monitor>Metering
See also:
16
17
Analog In1 Value
Analog In2 Value
Range:
4.000 to 20.000 mA [0.001 mA]
-/+10.0 V [0.1 V]
Default:
Read Only
Access:
1
Path: Monitor>Metering
See also:
320
Value of:
If Parameter 320
=.xx00
If Parameter 320 =
.xx11
Analog In1
volts (terminals 14/15)
mA (terminals 16/17)
Analog In2
volts (terminals 18/19)
mA (terminals 20/21)
Summary of Contents for Reliance electric 6SP201-015
Page 14: ...1 2 SP600 AC Drive User Manual ...
Page 54: ...Mounting the Drive 3 16 ...
Page 82: ...6 12 SP600 AC Drive User Manual ...
Page 96: ...7 14 SP600 AC Drive User Manual ...
Page 232: ...Parameter Descriptions 12 102 ...
Page 280: ...B 8 SP600 AC Drive User Manual ...
Page 282: ...C 2 SP600 AC Drive User Manual ...
Page 284: ...D 2 SP600 AC Drive User Manual ...
Page 298: ......
Page 299: ......