Maintenance
Repair
124
MagneMotion
Rockwell Automation Publication MMI-UM013B-EN-P - April 2020
If the node controller being replaced had eight or fewer connections, only one NC-S is
required for replacement. If the connections used only Ports 1–8, no changes are required. If
any connections used Ports 9–12, those connections must be reconfigured to one of the avail-
able ports on the NC-S.
When redistributing the connections, make sure that all connections for a node are made to the
same node controller.
1.
Run the MagneMotion Configurator and open a copy of the current Node Controller
Configuration File.
2.
In the
Node Controllers
section of the
Configuration Tree
, open the
Node Control-
ler Details
page for the node controller being replaced.
•
Remove ownership of those nodes that are connected to Comm Ports 9–12.
3.
In the
Node Controllers
section of the
Configuration Tree
, add a new node control-
ler.
A.
Set the IP address of the new node controller to match the IP address of the
second NC-S added.
B.
Take ownership of those nodes that were connected to Comm Ports 9–12.
C.
Select the appropriate Comm Port for each connection.
4.
Save the revised Node Controller Configuration File with a new name to identify it.