26
Publication CC-QS015A-EN-P - November 2009
Chapter 2
System Validation and Application Tips
Follow These Steps
Validate Proper Operation of the Safety Systems
To confirm that the system is operating properly, you need to perform a series of tests.
Start Up
1.
Apply power to the system.
2.
Check the following:
•
The 100S contactors do not energize.
•
Guarded motion does not start.
•
The red stacklight is on.
3.
Press and release the Start-Reset button.
4.
Check the following:
•
The 100S contactors energize.
•
Guarded motions starts.
•
The green stacklight is on.
E-stop Function
1.
Press the E-stop.
2.
Check the following:
•
The two 100S contactors de-energize.
•
Guarded motion stops.
•
The red stacklight is on.
Start
Validate Proper Operation of the