Publication CC-QS015A-EN-P - November 2009
21
Product Integration
Chapter 1
13.
On the OptiLink Communication dialog box,
select Compatibility mode.
14.
Choose the Comport assigned by Windows
Device Manager.
15.
Click OK.
16.
From the File menu, choose PC->MSR42 (Download).
17.
When prompted, type the password ‘ABGM’.
18.
On the Controller Description dialog box, type
the six-digit Device number and click OK.
19.
Cycle power to the MSR42 relay to allow the
download to proceed.
Once the download is complete, the Configuration control document dialog box appears.