Publication CC-QS015A-EN-P - November 2009
29
System Validation and Application Tips
Chapter 2
Mute Dependent Override (from Right)
1.
While the load is still disrupting the light curtain beam from the previous mute error test,
press and release the Start-Reset button.
2.
Check the following:
•
The safety output turns on.
•
The two 100S contactors energize.
•
Guarded motion starts.
•
The muting lamp is on and is not blinking.
•
The green stacklight turns on.
3.
As soon as the load clears the light curtain, break the light curtain beam, taking care not to
block any sensors.
4.
Check the following:
•
The safety output turns off.
•
The two 100S contactors de-energize.
•
Guarded motion stops.
•
The red stacklight turns on.
5.
Press and release the Start-Stop button to start the system.
Muting Error (from Left)
1.
From the left, let a load pass S4 and S3, but stop it short of the light curtain sensing field.
2.
Confirm that the muting lamp turns on.
3.
Wait the configured t(espe) delay for the muting lamp to start blinking.
4.
Move the load forward to break the light curtain beam.
5.
Check the following:
•
The safety output turns off.
•
The two 100S contactors de-energize.
•
Guarded motion stops.
•
The red stacklight turns on.