16
Publication CC-QS015A-EN-P - November 2009
Chapter 1
Product Integration
7.
From the Inputs GPIO pull-down menu, choose Muting Micro 400.
8.
Click OK on the safety notice dialog box.
9.
On the Muting dialog box, click 4 sensor T-type.
This dialog box helps you configure your muting system properly.
The Muting dialog box shows that a load on the conveyor travels left-to-right, passing in
sequence through the first two muting sensors and the LC (light curtain). After passing the
light curtain, the load passes, in sequence, the last two sensors. An object passing the
sensors in the proper sequence and within the configured time constraints is permitted to
pass though the light curtains without triggering a safe stop. The light curtains are ignored
by the safety system until the object passes completely through, clearing the light curtain
sensing field and passing the third sensor, ending the muting period.
As soon as the third sensor is cleared, the safety system will again trigger a safe stop if
anything breaks the sensing field without first passing S1 and S2 in the proper order and
within the configured time constraints.
10.
Click Help in the lower right corner of the Muting dialog box.